Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
To support VT_BSTR items e.g. for signaling a state, these strings must be
translated in a unique number which can be handled by SX Open. These strings
have to be mapped to hash values in SX Configurator (see Hash VT_BSTR
sheet). The same hashing function will be used in SX Open as soon as string is
received from OPC Client. By defining a mapping function which knows about the
different hash values a mapping of strings to a discrete set of numbers is possible.
For direction OPC mapping function which is used to map a BACnet property to an
OPC item must be entered. For direction BACnet or Twoway mapping function
which is used to map an OPC item to a BACnet property must be entered
For more information on the functions for signal and function mapping refer to the
Engineering Guideline [1].
5.2.11 Setting default values
Figure 5-28
To reduce the amount of work in entering values in Configuration sheet, default
values will be used whenever a field has been left blank. The default value can be
assigned by entering a value in column default of Properties sheet. If this field is
left blank, too, a build in default will be used.
2)
H<…>
Important