Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
5.2.2 BACnet section
Figure 5-14
The BACnet information has to be entered manually to define each mapped OPC
item.
In the simplest case, some (or all) OPC items are mapped to [PrVal] of the BACnet
objects.
This is the case if the following conditions apply to each OPC-item row in the
Configuration sheet:
Item Set Ref is blank
BACnet Device Reference exists
Object Type is defined
Object Instance has been entered
Keyname exists
Object Name exists
Column Description
BACnet Device Ref
Reference to a specific BACnet device in the BACnet Device sheet to which the
BACnet object is be assigned There are as many BACnet devices as required. For
further information, see
1)
BACnet Object Type
Type of BACnet object. See the Objects sheet, section 5.9.
Select an appropriate object for value mapping on the BACnet side in accordance with
the OPC-side data type and access rights.
Normally, integers and real values are mapped to analog, binary and multistate
objects, and read access and write access to input and output objects respectively.
Object Instance
Instance of the object.
The instance must be unique for each object type and BACnet device, i.e. for each
device, there can be only one analog input object 1.
Keyname
This is normally identical to the BACnet object name. Governed by the Desigo Insight
naming conventions. Automatically derived from the OPC item name during OPC
import, provided the option Suggest BACnet Object Name and Keyname is enabled.
The key name is interpreted on the Desigo-side as the User Designation.