ANCB/DN Specifications
Protocol and Addressing Open Systems standard TCP/IP protocol and addressing
(Transmission Control Protocol/Internet Protocol); Full Class A, B and
C addresses and subnet masking supported
Wiring Connections
Two part connectors with screw-terminals provided for cable
connection
Fiber Optic Coupler for Fiber Optic Connections
DataNET Option, Standard
Cable
Cable connection by Belden 9182 (single pair) or Belden
SSD1743 (two pairs) or equivalent; two pairs of wires are
required to support redundancy
Two pairs of cable is required to support redundancy
Shielded cable or unshielded cable in conduit is required for
conformance to CE certified installation
Two part connectors with screw-terminals provided for field
connection
DataNET Option, Fiber Optic
Cable
Fiber optics connection by 62.5 multi-mode cable corresponding
to 10BaseFL Ethernet specification
Two pairs of fibers are required to support redundancy
Type ST mating connectors provided for field connection
Approximately 3 mbps base transmission rate; uses dedicated
transmission technique that does not require collision detection to
achieve high data throughput efficiency
Maximum Length 5000 feet ( 1.7km)
Fiber Optic Coupler
Two (Tx, Rx) ST-Style Connectors (Amp type 2.5mm Bayonet)
Serial Port
Standard RS-232 port for attachment of a laptop computer, for
configuring IP Addresses and troubleshooting.
Communication
Comparisons
The Table below compares key communication features between using
Advance Data Hiway, Ethernet, or DataNET.
Feature Advance Data Hiway Ethernet DataNET
Speed 14.2 KB/Sec 10 M baud 2. 048 M baud
Redundant Yes No Yes
Number of Units in
Maxum System
248 1200 1200
2000592-001 Installation 3