DataNET Troubleshooting Guide, Continued
Configuration
Parameter Errors
The device may have an invalid or duplicate IP address, Subnet mask or
iproute. Each ANCB must have a
unique IP address. Verify the
configuration parameters by connecting a PC serial port to the
Configuration Port, Logging in and typing config display.
local> config display
Config:
Device ANCB_DN
address ip 172.16.9.239
netmask 255.255.0.0
address ethernet 00.c0.c9.00.d2.3b
iproute 0.0.0.0
time server ip 0.0.0.0
port1 DataNET Copper
port2 DataNET Copper
Device ID
The ANCB/DN device id is automatically assigned and is not user
configurable as it is on the DataNET Hub. Th ANCB/DN device ID is
automatically set to the board IP address at power up or reset. :
Broadcast Status
Information
The Advance Network device periodically broadcast their status for
diagnostic and network routing purposes.
2000592-001 Troubleshooting 53