Siemens SED2 User Manual Page 61

  • Download
  • Add to my manuals
  • Print
  • Page
    / 130
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 60
Parameter Details (Numeric Listing)
Siemens Building Technologies, Inc. 53
P0777[2] Value x1 of analog output scaling Level 2
Min: -99999.9 Def: 0.0 Max: 99999.0
Unit: %
Details:
Defines x1 output characteristic in %. The scaling block is responsible for
adjustment of the analog output value defined in P0771 (analog output).
Parameters of the analog output scaling block (P0777 to P0781) work as follows:
P0780
y2
P0778
y1
20 mA
0
(-100%)
P0777
x1
P0779
x2
100%
20
Output signal (mA)
Where:
Points P1 (x1, y1) and P2 (x2, y2) can be chosen freely.
Index:
P0777[0]: Analog output 1 (AO1)
P0777[1]: Analog output 2 (AO2)
Example:
The default values of the scaling block provide a scaling of
P1: 0.0%=0 mA or 0V and P2: 100.0%=20 mA or 20V.
Dependency:
Effects P2000 to P2002 (referency frequency, voltage, current or torque)
depending on which setpoint is to be generated.
P0778[2] Value y1 of analog output scaling Level 2
Min: 0 Def: 0 Max: 20
Unit: -
Details:
Defines y1 of output characteristic.
Index:
P0778[0]: Analog output 1 (AO1)
P0778[1]: Analog output 2 (AO2)