SED2 VFD Parameter Reference Guide
48 Siemens Building Technologies, Inc.
P0756[2] Type of analog input Level 2
Min: 0 Def: 0 Max: 5
Unit: -
Details:
Defines type of analog input and also enables analog input monitoring.
To change from a voltage to a current analog input, modify parameter P0756 as
well as set I/O module DIP switches to the appropriate position. The DIP switch
settings are as follows:
- OFF=voltage input (10V)
- ON=current input (20 mA)
Allocation of DIP switches to analog inputs is as follows:
- DIP switch on left (DIP1)=Analog input 1
- DIP switch on right (DIP2)=Analog input 2
Enum:
0 Unipolar voltage input (0V to +10V)
1 Unipolar voltage input with monitoring (0 to 10V)
2 Unipolar current input (0 mA to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
5 L+S NI1000 sensor input
Index:
P0756[0]: Analog input 1 (AI1)
P0756[1]: Analog input 2 (AI2)
Dependency:
This function is disabled if the analog scaling block is programmed to output
negative setpoints (see P0757 to P0760 for analog input scaling).
Note:
When monitoring is enabled and a deadband is defined (P0761), a fault condition
will be generated (F0080) if the analog input voltage falls below 50% of the
deadband voltage.
When using a value of 5, any PID setpoint needs to be in degrees C.
Reference:
See P0757 to P0760 (analog input scaling).