SED2 VFD Parameter Reference Guide
98 Siemens Building Technologies, Inc.
P2188 Lower torque threshold 2 Level 3
Min: 0.0 Def: 0.0 Max: 99999.0
Unit: Nm
Details:
Lower limit threshold value 2 for comparing actual torque.
Reference:
See P2182 (belt threshold frequency 1).
P2189 Upper torque threshold 3 Level 3
Min: 0.0 Def: 99999.0 Max: 99999.0
Unit: Nm
Details:
Upper limit threshold value 3 for comparing actual torque.
Reference:
See P2182 (belt threshold frequency 1).
P2190 Lower torque threshold 3 Level 3
Min: 0.0 Def: 0.0 Max: 99999.0
Unit: Nm
Details:
Lower limit threshold value 3 for comparing actual torque.
Reference:
See P2182 (belt threshold frequency 1).
P2191 Belt failure speed tolerance Level 3
Min: 0.00 Def: 3.00 Max: 20.00
Unit: Hz
Details:
P2191 defines the allowed speed variation bandwidth between the SED2
frequency, and the speed reference from the pulse train. When the speed of the
SED2 varies by more than this amount, a trip or warning occurs.
P2192 Time delay for belt failure Level 3
Min: 0 Def: 10 Max: 65
Unit: s
Details:
P2192 defines a delay before a warning/trip becomes active. It is used to
eliminate events caused by transient conditions. It is used for both methods of
fault detection.