SED2 VFD Parameter Reference Guide
106 Siemens Building Technologies, Inc.
P2221[2] BI: Fixed PID setpoint select Bit 1 Level 3
Min: 0:0 Def: 0:0 Max: 4000:0
Unit: -
Details:
Defines command source of fixed PID setpoint selection Bit 1.
Index:
P2221[0]: 1st Command data set (CDS)
P2221[1]: 2nd Command data set (CDS)
Settings:
722.0=Digital input 1 (requires P0701 to be set to 99, BiCo)
722.1=Digital input 2 (requires P0702 to be set to 99, BiCo)
722.2=Digital input 3 (requires P0703 to be set to 99, BiCo)
722.3=Digital input 4 (requires P0704 to be set to 99, BiCo)
722.4=Digital input 5 (requires P0705 to be set to 99, BiCo)
722.5=Digital input 6 (requires P0706 to be set to 99, BiCo)
P2222[2] BI: Fixed PID setpoint select Bit 2 Level 3
Min: 0:0 Def: 0:0 Max: 4000:0
Unit: -
Details:
Defines command source of fixed PID setpoint selection Bit 2.
Index:
P2222[0]: 1st Command data set (CDS)
P2222[1]: 2nd Command data set (CDS)
Settings:
722.0=Digital input 1 (requires P0701 to be set to 99, BiCo)
722.1=Digital input 2 (requires P0702 to be set to 99, BiCo)
722.2=Digital input 3 (requires P0703 to be set to 99, BiCo)
722.3=Digital input 4 (requires P0704 to be set to 99, BiCo)
722.4=Digital input 5 (requires P0705 to be set to 99, BiCo)
722.5=Digital input 6 (requires P0706 to be set to 99, BiCo)
P2223[2] BI: Fixed PID setpoint select Bit 3 Level 3
Min: 0:0 Def: 722:3 Max: 4000:0
Unit: -
Details:
Defines command source of fixed PID setpoint selection Bit 3.
Index:
P2223[0]: 1st Command data set (CDS)
P2223[1]: 2nd Command data set (CDS)
Settings:
722.0=Digital input 1 (requires P0701 to be set to 99, BiCo)
722.1=Digital input 2 (requires P0702 to be set to 99, BiCo)
722.2=Digital input 3 (requires P0703 to be set to 99, BiCo)
722.3=Digital input 4 (requires P0704 to be set to 99, BiCo)
722.4=Digital input 5 (requires P0705 to be set to 99, BiCo)
722.5=Digital input 6 (requires P0706 to be set to 99, BiCo)