SED2 VFD Parameter Reference Guide
118 Siemens Building Technologies, Inc.
P2374 Motor staging delay Level 3
Min: 0 Def: 30 Max: 650
Unit: s
Details:
Time that PID error P2273 must exceed motor staging hysteresis P2373 before
staging occurs.
P2375 Motor destaging delay Level 3
Min: 0 Def: 30 Max: 650
Unit: s
Details:
Time that PID error P2273 must exceed motor staging hysteresis P2373 before
destaging occurs.
P2376 Delay override Level 3
Min: 0.0 Def: 25.0 Max: 200.0
Unit: %
Details:
P2376 as a percentage of PID setpoint. When the PID error P2273 exceeds this
value, a motor is staged/destaged irrespective of the delay timers.
P2377 Delay override lockout timer Level 3
Min: 0 Def: 30 Max: 650
Unit: s
Details:
Time for which delay override is prevented after a motor has been staged or
destaged.
This prevents a second staging event immediately after a first, being caused by
the transient conditions after the first staging event.
Note:
The value of this parameter must always be larger than staging hysteresis
P2373.
P2378 Staging frequency f, %fMax Level 3
Min: 0.0 Def: 50.0 Max: 120.0
Unit: %
Details:
The frequency as a percentage of maximum frequency. During a (de) staging
event, as the SED2 ramps from maximum to minimum frequency (or vice versa)
this is the frequency at which the relay (DO) is switched.