SED2 VFD Parameter Reference Guide
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
8 Siemens Building Technologies, Inc.
r0774 Actual analog output value
(V or mA)
— — — — 3
P0776 Type of analog output — 0 1 1 3
P0777 Value x1 of analog output
scaling
% —
99999.0
0.0 99999.0 2
P0778 Value y1 of analog output
scaling
— 0 0 20 2
P0779 Value x2 of analog output
scaling
% —
99999.0
100.0 99999.0 2
P0780 Value y2 of analog output
scaling
— 0 10 20 2
P0781 Width of analog output
deadband
— 0 0 20 3
Setpoint Channel and Ramp
Generator (P0004=10)
Parameter Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display
(defined in P0005)
— — — — All
P0003 User access level to
parameters
— 0 1 4 1
P0004 Parameter filter — 0 0 22 1
P0010 Commissioning
parameter filter
— 0 0 30 1
P1000 Selection of frequency
setpoint
— 0 2 77 1
P1001 Fixed frequency 1 Hz —650.0 0.00 650.00 2
P1002 Fixed frequency 2 Hz —650.0 5.00 650.00 3
P1003 Fixed frequency 3 Hz —650.0 10.00 650.00 3
P1004 Fixed frequency 4 Hz —650.0 15.00 650.00 3
P1005 Fixed frequency 5 Hz —650.0 20.00 650.00 3
P1006 Fixed frequency 6 Hz —650.0 25.00 650.00 3
P1007 Fixed frequency 7 Hz —650.0 30.00 650.00 3
P1008 Fixed frequency 8 Hz —650.0 35.00 650.00 3
P1009 Fixed frequency 9 Hz —650.0 40.00 650.00 3
P1010 Fixed frequency 10 Hz —650.0 45.00 650.00 3
P1011 Fixed frequency 11 Hz —650.0 50.00 650.00 3
P1012 Fixed frequency 12 Hz —650.0 55.00 650.00 3
P1013 Fixed frequency 13 Hz —650.0 60.00 650.00 3
P1014 Fixed frequency 14 Hz —650.0 65.00 650.00 3