SED2 VFD Parameter Reference Guide
20 Siemens Building Technologies, Inc.
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent
changes to user-defined parameter list. Then, set P0003=0 to activate the user-
defined parameter list.
When locked and when the user-defined parameter is activated, the only way to
exit the user-defined parameter list (and to view other parameters) is to set
P0012 ("key") to the value in P0011 ("lock").
Note:
Alternatively, set P0010=30 (commissioning parameter filter, factory setting) and
P0970=1 (factory reset) to perform a complete factory reset.
The default values of P0011 ("lock") and P0012 ("key") are the same.
r0018 Firmware version Level 3
Min: - Def: - Max: -
Unit: -
Details:
Displays version number of installed firmware.
r0019 CO/BO: BOP control word Level 3
Min: - Def: - Max: -
Unit: -
Details:
Displays status of operator panel commands.
The following settings are used as the "source" codes for keypad control when
connecting to BiCo input parameters.
Bitfields:
Bit00 ON/OFF1 0 NO 1 YES
Bit02 Reserved
Bit03 Reserved
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit08 JOG right 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit12 Hand Operation 0 NO 1 YES
Bit13 Motor potentiometer up 0 NO 1 YES
Bit14 Motor potentiometer down 0 NO 1 YES
Bit15 Auto Operation 0 NO 1 YES
Note:
When BiCo technology is used to allocate functions to panel buttons, this
parameter displays the actual status of the relevant command.
The following functions can be "connected" to individual buttons:
ON/OFF1
OFF2
JOG
REVERSE
INCREASE
DECREASE