SED2 VFD Parameter Reference Guide
76 Siemens Building Technologies, Inc.
P1203 Search rate: Flying start Level 3
Min: 10 Def: 100 Max: 200
Unit: %
Details:
Sets factor by which the output frequency changes during flying start to
synchronize with turning motor. This value, is entered in % relative to the default
time factor, defines the initial gradient (and thus influences the time taken to
search for the motor frequency):
The search time is the time taken to search through all frequencies between
f_max + 2 × f_slip to 0 Hz.
P1203=100% is defined as giving a rate of 2% of f_slip,nom/ms.
P1203=200% would result in a rate of frequency change of 1% of f_slip,nom/ms.
Example:
For a motor with 50 Hz, 1350 rpm, 100% would produce a maximum search time
of 600 ms. If the motor is turning, the motor frequency is found in a shorter time.
Note:
A higher value produces a flatter gradient and thus a longer search time. A lower
value has the opposite effect.
P1210 Automatic restart Level 3
Min: 0 Def: 1 Max: 5
Unit: -
Details:
Enables restart after a supply power break or after a fault.
Enum:
0 Disabled
1 Trip reset after power on P1211 disabled
2 Restart after supply power blackout P1211 disabled
3 Restart after brownout or fault P1211 enabled
4 Restart after supply power brownout P1211 disabled
5 Restart supply power after blackout or fault P1211 disabled
Dependency:
Auto restart requires constant ON command (such as via a digital input wire link).
CAUTION:
Settings 2 to 5 can cause the motor to restart unexpectedly.
Note:
P1200 flying start must be used in cases where the motor may still be turning
(such as after a short supply power break) or can be driven by the load.
A supply power brownout is when the power is interrupted and reapplied
before the operator panel display has gone dark. It is a very short supply power
break where the DC link has not fully collapsed.
A supply power blackout is when the operator panel display has gone dark
before the power is reapplied. It is a long supply power break where the DC link
has fully collapsed.