S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
5-22 A5E00105475-03
 6DPSOHRIUHVSRQVHWLPHFDOFXODWLRQ
$VVHPEO\
You have configured an S7shy300 and equipped it with following modules in two
racks:
a CPU 314C-2
Configuring the cycle load as a result of communication: 40 %
4 digital input modules SM 321; DI 32 x 24 VDC (4 bytes each in the PI)
3 digital output modules SM 322; DO 16 x 24 VDC/0.5 A (2 bytes each in the
PI)
2 analog input modules SM 331; AI 8 x 12-bit (not in the PI)
2 analog output modules SM 332; AO 4 x 12-bit (not in the PI)
8VHUSURJUDP
According to the instruction list, the user program runtime is 10.0 ms.
&DOFXODWLQJWKHF\FOHWLPH
In this example, the cycle time is equivalent to the sum of following times:
User program processing time:
approx. 10 ms x CPU-specific factor 1.10 = approx. 11 ms
Process image transfer time
Process image of inputs: 100
µs + 16 bytes x 37 µs = approx. 0.7 ms
Process image of outputs: 100
µs + 6 bytes x 37 µs = approx. 0.3 ms
Operating system runtime at the scan cycle checkpoint:
approx. 0.5 ms
The sum of the listed times is equivalent to the cycle time:
&\FOHWLPH= 11.0 ms + 0.7 ms + 0.3 ms + 0.5 ms = 12.5 ms.
&DOFXODWLQJWKHSK\VLFDOF\FOHWLPH
Under consideration of communication load:
12.5 ms * 100 / (100-40) = 20.8 ms.
Thus, under consideration of time-sharing factors, the DFWXDOF\FOHWLPHis PV.