&\FOHDQGUHVSRQVHWLPHV
S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
5-20 A5E00105475-03
 5HSURGXFLELOLW\RIGHOD\LQWHUUXSWVDQGZDWFKGRJLQWHUUXSWV
'HILQLWLRQRIUHSURGXFLELOLW\
'HOD\LQWHUUXSW:
The period that expires between the call of the first instruction in the interrupt OB
and the programmed time of interrupt.
:DWFKGRJLQWHUUXSW:
The fluctuation width of the interval between two successive calls, measured
between the respective initial instructions of the interrupt OBs.
5HSURGXFLELOLW\
The following times apply for the CPUs described in this manual:
Delay interrupt: +/- 200 µs
Watchdog interrupt: +/- 200 µs
These times only apply if the interrupt can actually be executed at this time and if
not interrupted, for example, by higher-priority interrupts or queued interrupts of
equal priority.