0HPRU\FRQFHSW
S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
A5E00105475-03
4-5
 0HPRU\IXQFWLRQV
,QWURGXFWLRQ
Memory functions are used to generate, modify or delete entire user programs or
specific blocks. You can also ensure that your data is retained by archiving your
own project data.
*HQHUDO%DVLFVRIGRZQORDGLQJDXVHUSURJUDPYLD3*3&
All user program data is downloaded from your PG/PC to the CPU via MMC.
Blocks use the load memory area as specified under "Load memory requirements"
in "General block properties".
Load Memory Work Memory
Stored on hard drive
Code blocks
Data blocks
Comments
Symbols
Code blocks
Data blocks
Parts of code and
data blocks required
for startup *
MMC
PG
6ES7 953-8Lx00-0AA0
M
i
c
r
o
M
e
m
o
r
y
C
a
r
d
S
I
M
A
T
I
C
64k Byte
CPU
Figure 4-2 Load memory and RAM
* If the RAM is not completely retentive, the retentive portion of the RAM is
displayed as retentive memory in the STEP 7 module status (as with
CPU 317-2 DP).
You cannot run the program until all the blocks have downloaded.
1RWH
This function is only permitted when the CPU is in STOP mode.
Load memory is empty if this load operation could not be interrupted due to power
loss or illegal block data.