6SHFLILFDWLRQVIRULQWHJUDWHG,2V&38[&RQO\
S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
7-14 A5E00105475-03
7
0 Bit No.
reserved
Unit of measurement
reserved
00 :
01 :
10 :
Default setting: 00
B
B
B
B
Celsius
Fahrenheit
Kelvin
Integration time interference frequency suppression channel AI 0
7
0 Bit No.
00 :
01 :
10 :
Default setting: 10
B
B
B
B
2.5 ms, 400 Hz
16.6 ms, 60 Hz
20 ms, 50 Hz
Measuring range channel AI 0 (settings see byte 6)
Measuring method channel AI 0 (settings see byte 6)
7
0 Bit No.
7
0 Bit No.
7
0 Bit No.
Measuring range channel AI 3
Measuring method AI 3
7
0 Bit No.
0:
H
H
H
H
1:
2
3:
Default setting: 1
H
:
deactivated
U Voltage
I Current
I Current
0:
2:
3:
4:
8:
9:
Default setting: 9
H
H
H
H
H
H
H
deactivated
0 … 20 mA
4 … 20 mA
+/- 20 mA
0 … 10 V
+/- 10V
Measuring range channel AI 3
Measuring method channel AI 4
7
0 Bit No.
0:
H
H
H
H
6:
15 :
Default setting 6
deactivated
resistance
bulb resistor
0:
2:
6:
Default setting: 2
H
H
H
H
deactivated
600 Ohm
Pt 100
Byte 0
Byte 1
Byte 2 reserved
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8 to 10 reserved
Integration time interference frequency suppression channel AI 1
Integration time interference frequency suppression channel AI 2
Integration time interference frequency suppression channel AI 3
Measuring range channel AI 1 (settings see byte 6)
Measuring method channel AI 1 (settings see byte 6)
Measuring range channel AI 2 (settings see byte 6)
Measuring method channel AI 2 (settings see byte 6)