S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
8-6 A5E00105475-03
1RWH
The user program can only be downloaded and thus the CPU can only be used if
the MMC is inserted.
3*23IXQFWLRQV
With CPUs 315-2 DP (6ES7315-2AFx3-0AB0), 316-2DP and 318-2 DP, PG/OP
functions at the DP interface were only possible if the interface was set to active.
With CPUs 31xC/31x, these functions are possible at both active and passive
interfaces. The performance of the passive interface is considerably lower,
however.
5RXWLQJIRUWKH&38[&[DVDQLQWHOOLJHQWVODYH
If you use the CPU 31xC/31x as an intelligent slave, the routing function can only
be used with an actively-configured DP interface.
In the properties of the DP interface in STEP 7, tick the Commissioning / Test
mode check box.
&KDQJHGUHWHQWLYHUHVSRQVHIRU&38'3
For data blocks for CPU 317-2 DP
you can set the retentive response in the block properties of the DB (as of
STEP 7, V5.2 + SP 1).
using SFC 82 “CREA_DBL“ -> Parameter ATTRIB, Bit NON_RETAIN, you can
specify if the actual values of an OB should be maintained at POWER OFF/ON
or STOP-RUN (retentive DB) or if the start values should be read from the load
memory (non-retentive DB):