6SHFLILFDWLRQV
S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x
6-20 A5E00105475-03
6SHFLILFDWLRQV
IEC Timers Yes
Type SFB
Number unlimited (limited only by RAM size)
'DWDDUHDVDQGWKHLUUHWHQWLYLW\ &38&3W3 &38&'3
flag bits 256 bytes
Retentive memory Configurable
Retentivity is default setting MB0 to MB15
Clock memory bits 8 (1 byte per memory bit)
Data blocks max. 511
(DB 1 to DB 511)
Size max. 16 KB
Local data per priority class max. 510 bytes
%ORFNV &38&3W3 &38&'3
Total 1024 (DBs, FCs, FBs)
The maximum number of blocks that can be loaded may be
reduced if you are using another MMC.
OBs See the Instruction List
Size max. 16 KB
Nesting depth
per priority class 8
additional within an error OB 4
FBs max. 512
(FB 0 to FB 511)
Size max. 16 KB
FCs max. 512
(FC 0 to FC 511)
Size max. 16 KB
$GGUHVVDUHDV,2V &38&3W3 &38&'3
Total I/O address area max. 1024 bytes/1024 bytes
(can be freely addressed)
max. 1024 bytes/1024 bytes
(can be freely addressed)
Distributed None max. 1008 bytes
I/O process image 128 bytes/128 bytes 128 bytes/128 bytes
Digital channels max. 1008 max. 8192
of those local max. 992 max. 992
integrated channels 16 DI / 16 DO 16 DI / 16 DO
Analog channels max. 248 max. 512
of those local max. 248 max. 248
integrated channels None None