7 Background information
28
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
Copyright © Siemens AG 2010 All rights reserved
7.3.4 STARTER - carrying out a motor identification routine
After completing the quick commissioning, alarm A0541 (Motor data-
identification active) is displayed. Please carefully note that when starting the
motor identification routine current flows in the motor. For hanging (suspended)
axes the load must always be supported.
To start the motor data identification routine, in the Project Navigator select the
menu item Commissioning and activate by double clicking on Control panel.
Press Assume control priority and carefully note the security/safety
information and instructions. Then activate Enables.
1.) If the Control panel isn't completely displayed on your PG/PC, then press
the button.
The motor data identification routine is started by pressing the
button. Do
not exit the STARTER software and go to another task as otherwise the motor
data identification routine will be interrupted for safety reasons.
Please wait until the
button changes back to the button.
Return the control priority to the S7 control by pressing the
button.