7 Background information
24
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
Copyright © Siemens AG 2010 All rights reserved
7.2.2 DB1, Axis_DB
The Axis_DB represents the interface between the S7 program and the SINAMICS
G120 via FC100.
Axis_DB is generated from UDT 1 (Axis_DB_G120)
Principal structure of Axis_DB:
Address Symbolic name Type Function
Internal data
DBW0 Basic_Data.Moduleadress INT
I/O start address of the SINAMICS G120 (refer to
HW Config)
DBB3 Basic_Data.Drivetyp Byte Drive type, must be 2
S7 -> SINAMICS G120
DBW4 Control_signals.STW2 Bool Control word 2 (for details, refer to the S7 program)
DBW6 Control_signals.STW1 Bool Control word 1 (for details, refer to the S7 program)
DBW8 Control_signals.Frequency_set INT Frequency setpoint in x.x %
DBW10 Control_signals.Torque_set INT Torque setpoint in x.x %
SINAMICS G120 -> S7
DBW14 Status_signals.ZSW2 Bool Status word 2 (for details, refer to the S7 program)
DBW16 Status_signals.ZSW1 Bool Status word 1 (for details, refer to the S7 program)
DBW18 Status_signals.Actual_frequency INT Frequency actual value in x.x %
DBW20 Status_signals.Actual_current INT Current actual value (Value from SINAMICS G120)
DBW22 Status_signals.Actual_current_A INT Current actual value in x.xx A
Error messages
DBW24 Faults.Drive_error_number INT Actual error number of the SINAMICS G120
DBW26 Faults.Drive_alarm_number INT Actual alarm number of the SINAMICS G120
In this function example the individual data of the DB1 are supplied in FB10.