4 Configuration and wiring
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
11
Copyright © Siemens AG 2010 All rights reserved
4.3 Fault 395 (acceptance test / acknowledgement present)
Fault F395 is output when powering-up for the first time and after replacing the
Control Unit (CU) or the Power Module (PM).
This fault does not represent an incorrect drive inverter function. The reason for
this fault message is to monitor the individual drive inverter components (CU and
PM) to prevent them from being replaced by unauthorized personnel.
Acknowledging fault F395
Just like any other fault, it can be acknowledged using an appropriately
parameterized input, via the field bus or using the STARTER parameterizing
software.
4.4 Important hardware component settings
Most of the module/board settings are made in the HW Config in the software.
Hardware settings are only required for the following modules/boards.
The modules/boards must be set with the control system in a no-voltage state.
4.4.1 SM374 simulation module
This module can be operated as 16 x DO (output via LED), 16 x DI (input via
switch) or as combined 8 x DI / 8 x DO. The last combination is used in this
function description.
The function of the module is selected using a rotary switch behind the front cover
between the series of switches.
As shown in the following diagram set the function switches to the setting 8 x
Output 8 x Input.
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 30 31