7 Background information
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
27
Copyright © Siemens AG 2010 All rights reserved
7.3.2 Calling the STARTER parameterization tool
• Starting from the main path of the SIMATIC Manager, start the STARTER
parameterization software by selecting SINAMICS_G120 and double click on
Inbetriebnahme.
• Then, in the Project Navigator of the STARTER
parameterization software select the object G120 (1.) and press button
(2.)
to establish an online connection to the drive inverter.
7.3.3 STARTER - carrying out quick commissioning
• The screen form with the actual configuration is opened by double clicking on
Configuration in the Project Navigator.
• The quick commissioning Wizard is started after pressing the
button.
• Enter the appropriate values into the Control structure to Encoder screen
forms. You can call-up corresponding help texts in the individual screen forms
by pressing on the Help button.
• In the screen form Drive functions, select for Motor identification, the
function Ident. of al param. in standstill incl. the saturation curve (3).
• Enter the corresponding parameters into the Important parameters screen
form.
• In the screen form Calculation of the motor data, select Restore factory
setting and calculate motor data.
• In the screen form Summary do not
activate the function RAM -> ROM, but
instead press the Finish button.