7 Background information
SINAMICS G120 (CU240S DP) Control via PROFIBUS
V1.0, Beitrags-ID: 45288241
27
Copyright © Siemens AG 2010 All rights reserved
7.3.2 Calling the STARTER parameterization tool
Starting from the main path of the SIMATIC Manager, start the STARTER
parameterization software by selecting SINAMICS_G120 and double click on
Inbetriebnahme.
Then, in the Project Navigator of the STARTER
parameterization software select the object G120 (1.) and press button
(2.)
to establish an online connection to the drive inverter.
7.3.3 STARTER - carrying out quick commissioning
The screen form with the actual configuration is opened by double clicking on
Configuration in the Project Navigator.
The quick commissioning Wizard is started after pressing the
button.
Enter the appropriate values into the Control structure to Encoder screen
forms. You can call-up corresponding help texts in the individual screen forms
by pressing on the Help button.
In the screen form Drive functions, select for Motor identification, the
function Ident. of al param. in standstill incl. the saturation curve (3).
Enter the corresponding parameters into the Important parameters screen
form.
In the screen form Calculation of the motor data, select Restore factory
setting and calculate motor data.
In the screen form Summary do not
activate the function RAM -> ROM, but
instead press the Finish button.