Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Boiler 23. August 2007
In normal operation, minimum limitation of the boiler temperature is the lower limit value
of the controlled boiler temperature setpoint, depending on the boiler’s operating mode.
In normal operation, maximum limitation of the boiler temperature is the upper limit
value of the controlled boiler temperature setpoint and, at the same time, setpoint of the
electronic limit thermostat (TR).
The setting range of setpoint minimum and setpoint maximum is limited by the setpoint
of manual operation.
Example when using boiler operating mode “Automatic“:
20 10 0 -10 -20
40
30
60
50
80
70
TK
TK
TK
TK
SDK
2371Z26
TA
°C
°C
w
mi n
ma x
gem
0
Legend
TK Boiler temp
TKw Boiler temperature setpoint
...TKmax Maximum limitation of the
boiler temperature
Tkmin Minimum limitation of the
boiler temperature
SDK Switching diff
TAgem Composite outside
temperature
Minimum limitation of the return temperature
Line no. Operating line
2270 Return setpoint min
If the boiler return temperature falls below the return temperature setpoint, maintained
boiler return temperature becomes active.
Maintained boiler return temperature allows consumers to be influenced, control of a
bypass pump or use of a return temperature controller.
Output data
Line no. Operating line
2330 Output nominal
2331 Output of basic stage
These settings are required in the case of cascaded boilers with different outputs.
Return setpoint min