Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Heating circuits 23. August 2007
Optimum start / stop control
Line no. Operating line
HC1 HC2 HCP
790 1090 1390 Optimum start control max
791 1091 1391 Optimum stop control max
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint is reached at the relevant switching time.
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint minus 1/4 °C is reached at the relevant switching time
Optimum start / stop control is possible with or without room sensor.
Xein Switch-on time shifted forward in time
Xaus Switch-off time shifted forward in time
ZSP Time switch program
TRx Actual value room temp
TRw Room temperature setpoint
Raising the reduced setpoint
Line no. Operating line
HC1 HC2 HCP
800 1100 1400 Red setpoint increase start
801 1101 1401 Red setpoint increase end
The function is used primarily in connection with heating systems with only little spare
capacity (e.g. low-energy houses). In such cases, the heating up time would be too
long at low outside temperatures. When the Reduced setpoint is raised, the rooms are
prevented from cooling down to too low levels, thus shortening the heating up time
when changing to the Comfort setpoint.
Optimum start control max
Optimum top control max
0
24
2358Z02
Xein Xaus
TRx
TRw
ZSP
1/4 °C