Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Configuration 23. August 2007
Excess heat discharge
Active dissipation of excessive heat enables an external heat source to force
consumers (heating circuit, DHW storage tank, Hx pump) to draw excessive heat by
delivering a forced signal.
The parameter “Excessive heat draw“ can be used to determine for every consumer
whether or not it should take account of the "forced" signal, and hence whether or not
that consumer should participate in the dissipation of heat.
Local effect
When using LPB device address 0 or >1, excessive heat dissipation only acts on the
local consumers connected to the controller.
Central effect (LPB)
When using LPB device address = 1, excessive heat dissipation also acts on the
consumers connected to the other controllers in the same segment.
The distribution of excessive heat from segment 0 across other segments of the system
is not possible.
Mixing valve groups basic unit
Line no. Operating line
6014
6015
Function mixing group 1
Heating circuit 1/2
Return temp controller
Primary controller / system
pump
DHW primary controller
Instantaneous DHW heater
Return controller cascade
Cooling circuit 1
Heating circuit/cooling circuit 1
The mixing valve groups are assigned to the following connections:
Mixing valve group 1 Mixing valve group 2
Q2, Y1, Y2, B1 Q6, Y5, Y6, B12
Heating circuit 1/2
For this application, the respective settings of operating page “Heating circuit 1/2” can
be adapted.
Return temp controller
For this application, the respective settings of operating page “Boiler” can be adapted.
Primary controller / system pump
For this application, the respective settings of operating page “Primary controller /
system pump” can be adapted.
DHW primary controller
For this application, the respective settings of operating page “DHW storage tank” can
be adapted.
Instantaneous DHW heater
For this application, the respective settings of operating page “Instantaneous DHW
heater” can be adapted.
Return controller cascade
For this application, the respective settings of operating page “Cascade” can be
adapted.
RVS63.283 only