Siemens Albatros2 AVS37 User Manual Page 33

  • Download
  • Add to my manuals
  • Print
  • Page
    / 180
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 32
33/180
Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Power supply AVS16.290 23. August 2007
3.8.5 Checking the wireless components
To check whether the connections to the required system components are operational,
consult operating lines 130 through 135 on operating page “Wireless“ (operating level
“Commissioning“).
3.9 Power supply AVS16.290
Mounting notes
The boiler control panel is designed for installation in floor-standing or wall-hung oil or
gas boilers and may only be used for that purpose. For installation, the following points
must be observed:
Power to the control panel may be supplied only after the unit is completely fitted in
the cutout. Extension modules or dummy covers for which cutouts are provided must
also be fitted beforehand.
Dimensions of cutout 92 x 92 mm,
sheet metal thickness 0.5 to 3.0 mm
The boiler control panel can be secured with the 4 clips provided on the panel
Power to the control panel may be supplied only after the unit is completely fitted in
the cutout. Extensions or dummy covers for which cutouts are provided must also be
fitted beforehand.
The control panel wiring to the connection terminals does not feature strain relief and
must therefore be secured inside the boiler
The local regulations for electrical installation must be complied with
Mounting method
Installation Removal
2358Z27
2358Z28
2358Z29
Connections
Terminal Name
L Live AC 230 V blue
Protective earth green + yellow
N Neutral conductor blue
Terminal Name
1 L Live AC 230 V basic unit brown
2
Protective earth green + yellow
3 N Neutral conductor blue
4 L1 Live AC 230 V burner black
5 S3 Input burner fault -
Mains
Connection to basic unit
Page view 32