Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Solar 23. August 2007
DHW storage tank
During solar charging, preference is given to the DHW storage tank. At every level A, B
or C (see below), it is charged with priority. Only then will the other consumers of the
same level be charged. As soon as all setpoints of a level are attained, those of the
next level are approached, whereby priority is again given to the DHW storage tank.
Buffer storage tank
During solar charging, preference is given to the buffer storage tank. At every level A, B
or C (see below), it is charged with priority. Only then will the other consumers of the
same level be charged. As soon as all setpoints of a level are attained, those of the
next level are approached, whereby priority is again given to the buffer storage tank.
Storage tank setpoints:
Level DHW storage tank Buffer storage tank
Swimming pool
(1)
A 1610 Nominal setpoint Buffer setpoint (slave pointer)
2055 Setpoint solar heating
B 5050 Charging temp max 4750 Charging temp max
2055 Setpoint solar heating
C 5051 Storage tank temp
max
4751 Storage tank temp max
2070 Swimming pool temp
max
(1)
When priority for the swimming pool is activated (operating line 2065), the swimming
pool is charged before the storage tanks.
If the preferred storage tank cannot be charged in accordance with charging control,
priority is transferred to the next storage tank or the swimming pool for the period of
time set (e.g. too great temperature differential between collector and storage tank).
As soon as the preferred storage tank (according to setting "Charging priority storage
tank") is again ready to be charged, the transfer of priority will immediately be stopped.
If this parameter is disabled (---) charging proceeds in accordance with the "Charging
prio storage tank" settings.
During the period of time set, the transfer of priority will be delayed. This prevents
relative priority from intervening too frequently.
If solar output is sufficient and solar charging pumps are used, parallel operation is
possible. In that case, the storage tank of the priority model can be the next to be
simultaneously charged, in addition to the storage tank to be charged next. Parallel
operation can be delayed by introducing a waiting time. This way, in the case of parallel
operation, switching on of the storage tanks can be effected in steps.
The setting (---) disables parallel operation.
To remove any existing cold water in the primary circuit, operation of the secondary
pump of the external heat exchanger secondary pump can be delayed.
Start function
Line no. Operating line
3831 Min run time collector pump
3834 Collector start funct gradient
The collector pump remains on for at least the preset minimum run time.
When the temperature at the collector sensor rises, the collector pump is activated.
Charging time relative prio
Waiting time relative prio
Waiting time parallel op
Delay secondary pump
Min run time collector
pump
Collector start funct
gradient