Siemens Schweiz AG User Manual CE1U2354en
HVAC Products Configuration 23. August 2007
Heat gen shutoff valve Y4
If the buffer storage tank holds a sufficient amount of heat, the consumers can draw
their heat from it, and the heat sources need not be put into operation.
Automatic heat generation lock locks the heat sources and hydraulically disconnects
them from the rest of the plant with the help of heat source shutoff valve Y4.
This means that the heat consumers draw their energy from the buffer storage tank and
wrong circulation through the heat sources will be eliminated.
Solid fuel boiler pump Q10
For the connection of a solid fuel boiler, a circulating pump for the boiler circuit is
required.
Time program 5 K13
The relay is controlled according to the settings made in time program 5.
Buffer return valve Y15
This valve must be configured for return temperature increase / decrease or partial
charging of the buffer storage tank.
Solar pump ext exch K9
For the external heat exchanger, solar pump “Ext heat exchanger K9“ must be set at
the multifunctional relay output (QX).
If both a DHW and a buffer storage tank are available, operating line 5841 “External
solar heat exchanger“ must also be set.
Solar ctrl elem buffer K8
If several heat exchangers are used, the buffer storage tank must be set at the
respective relay output and, in addition, the type of solar controlling element must be
defined on operating line 5840).
Solar ctrl elem swi pool K18
If several heat exchangers are used, the swimming pool must be set at the respective
relay output and, in addition, the type of solar controlling element must be defined on
operating line 5840).
Collector pump 2 Q16
When using a second solar collector, a separate circulating pump for this collector
circuit is required.
H3 pump Q19
Pump H2 can be used for an additional consumer. Together with an external demand
for heat at input H2, it is possible to serve an air heater or similar.
Flue gas relay K17
If the flue gas temperature exceeds the level set on operating line 7053 "Flue gas
temperature limit", relay K17 closes.
Assisted firing fan K30
This setting has no function.
Cascade pump Q25
Common boiler pump for all boilers in a cascade.