Chapter 1
Introduction
RUGGEDCOM ROS
User Guide
14 ModBus Memory Map
Starting Address 2 Bytes 0x0000 to 0xFFFF
Number of Registers 2 Bytes 1 to 121 (0x79)
Section 1.6.2
ModBus Memory Map
The following details how ModBus process variable data is mapped.
Product Info
The following data is mapped to the Productinfo table:
Address #Registers Description (Reference Table in UI) R/W Format
0000 16 Product Identification R Text
0010 32 Firmware Identification R Text
0040 1 Number of Ethernet Ports R Uint16
0041 1 Number of Serial Ports R Uint16
0042 1 Number of Alarms R Uint16
0043 1 Power Supply Status R PSStatusCmd
0044 1 FailSafe Relay Status R TruthValue
0045 1 ErrorAlarm Status R TruthValue
Product Write Register
The following data is mapped to various tables:
Address #Registers Description (Reference Table in UI) R/W Format
0080 1 Clear Alarms W Cmd
0081 2 Reset Ethernet Ports W PortCmd
0083 2 Clear Ethernet Statistics W PortCmd
0085 2 Reset Serial Ports W PortCmd
0087 2 Clear Serial Port Statistics W PortCmd
Alarms
The following data is mapped to the alarms table:
Address #Registers Description (Reference Table in UI) R/W Format
0100 64 Alarm 1 R Alarm
0140 64 Alarm 2 R Alarm
0180 64 Alarm 3 R Alarm
01C0 64 Alarm 4 R Alarm
0200 64 Alarm 5 R Alarm