55/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Handling 11. May 2007
Operating line
user level
Function
Default value
Min
max
Unit
B4 ¦ Buffer sensor B41 ¦ Flue gas temp sensor B8 ¦
Common flow sensor B10 ¦ Solid fuel boiler sensor B22 ¦
DHW charging sensor B36 ¦ Buffer sensor B42 ¦
Common return sensor B73 ¦ Cascade return sensor
B70 ¦ Swimming pool sensor B13 ¦ Collector sensor 2
B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64
6041 I
Sensor input BX22
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return
sensor B7 ¦ DHW circulation sensor B39 ¦ Buffer sensor
B4 ¦ Buffer sensor B41 ¦ Flue gas temp sensor B8 ¦
Common flow sensor B10 ¦ Solid fuel boiler sensor B22 ¦
DHW charging sensor B36 ¦ Buffer sensor B42 ¦
Common return sensor B73 ¦ Cascade return sensor
B70 ¦ Swimming pool sensor B13 ¦ Collector sensor 2
B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None
6046
I Function input H2
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Excess heat discharge ¦ Release swimming
pool ¦ Heat request 10V ¦ Pressure measurement 10V
Optg mode changeover
HCs+DHW
6047
I Contact type H2
NC ¦ NO
NO
-
6048
I Min flow temp setpoint H2
70 8 120
°C
6050
I Temp value 10V H2
100 5 130
°C
6052
I Pressure value 3.5V H2
5.0 0.0 10.0
bar
6070
I Function output UX
None ¦ Boiler pump Q1 ¦ DHW pump Q3 ¦ DHW interm
circ pump Q33 ¦ Heat circ pump HC1 Q2 ¦ Heat circ
pump HC2 Q6 ¦ Heat circ pump HCP Q20 ¦ Collector
pump Q5 ¦ Solar pump ext exch K9 ¦ Solar pump buffer
K8 ¦ Solar pump swi pool K18 ¦ Collector pump 2 Q16 ¦
Boiler setpoint ¦ Output setpoint ¦ Heat request
None
6071
I Signal logic output UX
Standard ¦ Inverted
Standard
6075
I Temp value 10V UX
100 5 130
°C
6097
F Sensor type collector
NTC 10k ¦ Platinum 1000
NTC 10k
6098
F Readjustm collector sensor
0 -20 20
°C
6099
F Readjustm coll sensor 2
0 -20 20
°C
6100
F Readjustm outside sensor
0.0 -3.0 3.0
°C
6101
F Sensor type flue gas temp
NTC 10k ¦ Platinum 1000
NTC 10k
6102
F Readjustm flue gas sensor
0 -20 20
°C
6110
F Time constant building
15 0 50
h
6120
F Frost protection for the plant
Off ¦ On
Off
-
6128
F Heat request below OT
− − − − − − / -50 50
°C
6129
F Heat request above OT
− − − − − − / -50 50
°C
6131
F Heat req in economy mode
Off ¦ Only DHW ¦ On
Off
6200
I Sensors saving
No ¦ Yes
No
-