The 2x1 cascade is a special configuration of the basic unit, where the 2-stage boiler is
operated as 2 cascaded 1-stage boilers.
Due to the temperature differential between boiler temperature setpoint and boiler
temperature sensor B2 (common, mandatory cascade flow temperature sensor),
switching on / off of the lag boiler (release and reset integral) takes place according to
the control of a 2-stage burner. The same parameters are used.
If a boiler pump is required, QX1 and QX2 (operating lines 5890 and 5891) must be
appropriately set.
A common boiler pump can be operated at any other multifunctional relay output QX
parameterized as boiler pump Q1. The boiler pump of the lead boiler is always mapped
on these outputs.
With the configuration of the 2x1 cascade (parameter “Type of heat source”), the
following outputs and functions will be ready used or assigned.
Use Space Connector type
L1 Live burner P AGP8S.07A/109
Protective earth
N Neutral conductor
T1 Phase burner 1
T2 Burner 1 on
S3 Input burner fault
4
Input burner 1 hours run
EX2 Input burner 2 hours run Z AGP8S.04C/109
FX4
(T6)
Phase burner 2
QX4
(T7)
Burner 2 off
QX4
(T8)
Burner 2 on
Solar
Line no. Operating line
5840 Solar controlling element
Charging pump
Diverting valve
5841 External solar exchanger
Jointly
DHW storage tank
Buffer
In place of a collector pump and diverting valves for integrating the storage tanks, the
solar plant can also be operated with charging pumps.
2 x 1 cascade
Solar controlling element