RDG1...
RDG1...T RDG100T/H
Room thermostats with
LCD for wall mounting
RDG1…
for fan coil unit applications
for universal applications
for use with
compressors in dx type equipment
RDG100...: Operating voltage AC 230 V, On/Off, 3-pos. or PWM control outputs
RDG110: Operating voltage AC 230 V, On/Off relay (SPDT) outputs
RDG160T: Operating voltage AC 24 V, DC 0…10 V or On/Off control outputs,
DC 0…10 V or 1- / 3- speed
Operating modes: Comfort, Economy and Protection
Automatic or manual fan speed
Output for 1-speed, 3-speed or ECM fan DC 0...10 V (RDG160T)
3 multifunctional inputs for keycard contact, external sensor, etc.
Automatic or manual heating / cooling changeover
Adjustable commissioning and control parameters
Minimum and maximum setpoint limitation
Backlit display
Additional features of RDG100T, RDG160T, RDG100T/H:
Infrared remote control receiver
Auto Timer mode with 8 programmable timers
Auto timer can be disabled via P02
Auto timer can be disabled via DIP switches (only RDG160T)
Landscape design (only RDG100T/H)
Selectable relay output functions (RDG160T)
N3181en
2014-05-23
Building Technologies
Page view 0
1 2 3 4 5 6 ... 18 19

Summary of Contents

Page 1 - LCD for wall mounting

s 3181 RDG1... RDG1...T RDG100T/H Room thermostats with LCD for wall mounting RDG1… for fan coil uni

Page 2

Mounting and installation Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar rad

Page 3 - 1 2 3 4 5

• Recalibrate the temperature sensor if the room temperature displayed on the thermostat does not match the room temperature measured. To do this, c

Page 4

D1-GND Operating action Contact sensing Parallel connection of several thermostats for one switch Insulation against mains Select

Page 5

Function of inputs External room temperature sensor, heating/cooling changeover sensor, operating mode switchover contact, dewpoint monitor contact, e

Page 6

Reduction of hazardous substances 2011/65/EU EN50581 Safety class II as per EN60730 Pollution class Normal Degree of protection of housing IP30

Page 7

Connection terminals RDG100, RDG100T, RDG100T/H L X1 M X2 D1 GNDN Q1 Q2 Q3SELV L, N Operating voltage AC 230 V X1,

Page 8

Connection diagrams RDG100… N1 Room thermostat RDG100.. M1 1- or 3-speed fan V Valve actuators: On/Off or PWM, 3-position, heating, coolin

Page 9

RDG110… N1 Room thermostat RDG110.. M1 1- or 3-speed fan V Valve actuators: On/Off or PWM, 3-position, heating, cooling, radiator,

Page 10

RDG160T DC 0...10 V fan 1- / 3-speed fan Application V1  V2  • 2-pipe YHC • 2-p

Page 11

Dimensions 128.093.028.227.828.516.09.028.328.327.728.34.04.030.828.328.3 All dimensions in mm  2009-2014 Siemens Swi

Page 12

Use The RDG1… room thermostats are designed for use with the following types of system: Fan coil units via On/Off or modulating control outputs: • 2

Page 13 - Comfort mode (P08)

• 7-day time program: 8 programmable timers to switch over between Comfort and Economy mode (RDG100T, RDG160T, RDG100T/H) • Infrared remote control

Page 14

Applications, DIP setting, Control outputs • Chilled / heated ceiling 1 2 3 4 5 ONOFF • Chilled / heated ceiling and electric heater

Page 15 - N Q1 Q2 Q3

Applications, DIP setting, Control outputs • Heated or cooled with compressors 1 2 3 4 5 ONOFF • Heated or cooled with compressors wi

Page 16

Type summary Equipment combinations Description Product no. Data Sheet Infrared remote control IRA211 3059 Cable temperature or changeover sensor

Page 17

Electrical actuator, 3-position (for small valves 2.5 mm) SSP31… 4864 Electrical actuator, 3-position (for small valves 5.5 mm) SSB31... 4891 Elec

Page 18

Accessories Description Product no. Data Sheet Changeover mounting kit (50 pcs / package) ARG86.3 3009 Ordering Product no. Stock number Designation

Page 19

Display 1245678891011121314151617181920212332224 # Symbol Description # Symbol Description 1 Heating mode 14 Automatic fan 2 Heating mode auxili