Set_Prm Telegram DU Byte 3 – WD_Fact_2, Range 1 to 255
76543210
XXXXXXXX
WD_Fact_2
The watchdog is switched on or off via the WD_On bit of DU byte 1.
Bytes 2 & 3 are factors used for setting the watchdog control (T
WD
) time.
The watchdog time is calculated between 10ms and 650 seconds as follows:
T
WD
=10ms * WD_Fact_1 * WD_Fact_2. The watchdog control causes the
slave outputs to go to a failsafe state if the master fails to communicate with
the slave before this time expires.
Set_Prm Telegram DU Byte 4 – Min T
SDR
, Range 11 to 255 Tbit
76543210
XXXXXXXX
Min T
SDR
: Minimum time in Tbit (bit time) after which a slave is allowed to answer. This
value must be less than Max T
SDR
. 11 Tbits are specified permanently in the standard.
Byte 4 sets the minimum T
SDR
time (in bit time, 11-255) a slave will wait
before it is allowed to send a response to the master. If 00H is specified, the
previous or default value is used.
Set_Prm Telegram DU Byte 5 (Ident_Number, High Byte)
76543210
XXXXXXXX
Set_Prm Telegram DU Byte 6 (Ident_Number, Low Byte)
76543210
XXXXXXXX
The Ident_Number of the slave is transmitted for security purposes.
The Set_Prm parameters will not be accepted if this number does not match
that of the slave. However, the min T
SDR
can still be set if the Ident_number
doesn’t match and both the Lock_Req and Unlock_Req bits are set to 0.
Set_Prm Telegram DU Byte 7 (Group_Ident)
76543210
XXXXXXXX
Group_Ident
ProfiBus DP supports multi-cast messaging via a Global_Control
telegram function directed to a specific group of connected slaves identified
via this group number. Each bit represents a unique group. Note that
Group_Ident is only accepted if the Lock_Req bit is also set.
Set_Prm Telegram DU Bytes 8 to 32 or 244 (Optional, User_Prm_Data)
76543210
XXXXXXXX
Spec_User_Prm_Byte 8 (SPC3 ASIC related)
00000
WD_
Base
Dis_
Stopbit
Dis_
Startbit