Siemens SPC3 Specifications Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
Introduction To ProfiBus DP
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com
12
To give you an idea of what a GSD file might look like, consider the
following partial GSD file taken from Acromag Model 983PB-2012.
#Profibus_DP
GSD_Revision = 1 ; Version of the GSD file
Vendor_Name = “Acromag, Inc.” ; Vendor name
Model_Name = “983PB-2012” ; Product name
Revision = “A”
Ident_Number = 0x06F1 ; Ident Number
Protocol_Ident = 0 ; ProfiBus DP Only (1-DP/FMS)
Station_Type = 0 ; Type of device (Slave)
Hardware_Release = “A” ; Hardware version of the device
Software_Release = “A” ; Software version of the device
;
9.6_supp = 1 ; 9600bps Supported
19.2_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60 ; Maximum response time
MaxTsdr_19.2 = 60 ; at different baud rates.
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
;
Redundancy = 0 ; Redundancy Not Supported
Repeater_Ctrl_Sig = 2 ; Includes RTS Support w/TTL
Implementation_Type = “SPC3” ; Uses Siemens SPC3 ASIC
24V_Pins = 0 ; Does Not Include 24V
Fail_Safe = 1 ; Supports Fail-Safe Mode
Freeze_Mode_supp = 1 ; Supports FREEZE
Sync_Mode_supp = 1 ; Supports SYNC
Auto_Baud_supp = 1 ; Includes Auto Baud Detection
Set_Slave_Add_supp = 1 ; Addr can be set via ProfiBus
User_Prm_Data_Len = 3
User_Prm_Data = 0x00,0x00,0x00 ; Module Specific Parameters
; 00H = Set outputs to 0
; 01H = Maintain Last Output Values
; 02H = Set output to user-defined values in bytes 1 and 2
; Byte 1 is the lower byte of user-defined output data which is outputs 0 to 7
; Byte 2 is the upper byte of user-defined output data which is outputs 8 to 11
;
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 37 38

Comments to this Manuals

No comments