Introduction To ProfiBus DP
___________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com
23
DU Byte 1 (New_Slave_Add, 0-125)
76543210
XXXXXXXX
DU Byte 2 (Ident_Number for security check, High Byte)
76543210
XXXXXXXX
DU Byte 3 (Ident_Number for security check, Low Byte)
76543210
XXXXXXXX
The identification number (Ident_Number) is used to establish a
reference between a slave and its corresponding GSD file. This number is
assigned by the ProfiBus Trade Organization and cannot be changed. It is
used here for security purposes--if the ident_number does not match that of
the slave, the address will not be changed. Note that only class 2 masters
do not require an ident_number.
DU Byte 4 (LOCK - Enable/Disable Further Address Changes)
76543210
XXXXXXXX
00H = False/Unlocked, Change of address possible later.
01H = True/Lock, No further address changes possible
1
.
1
To unlock an Acromag module for address changes, set the external
switches to 255 (FFH) prior to applying power and this will clear the lock bit
and restore the internal EEPROM setting to 126. Next, simply set the
switches as desired from 0-125, or to 126 if you intend to use the Set-
Slave_Address command, and re-power the unit.
The parameter Status can be tested to indicate if the Set_Slave_Add
request frame was sent successfully and accepted by the slave. However,
the acknowledgement does not indicate whether the new values were
actually accepted by the slave. A master can check the correct execution of
this function by using Slave_Diag with the new DP-slave address and then
testing Status for the possible values of: OK, DS, NA, RS, RR, UE, and RE.
After completion of the power-on initialization routine and after the
slave’s address has been set to a valid address from 0-125, the slave will
proceed to the Wait_Prm state (Wait for Parameterization).
After the slave completes its power-on initialization routine and its
address has been set to a valid address from 0-125, the slave will proceed
to await the Parameterization Telegram (Set_Prm) from the master which
serves to identify the master for the slave and specify the slave’s operating
mode. The slave address must already be set to a valid address from 0-125
for a master to perform parameterization (Set_Prm). If the slave address is
instead set to 126, then it will await the Set Slave Address command before
proceeding. While awaiting the parameterization telegram, a slave will reject
all other telegrams except Slave_Diag or Get_Cfg.