Set_Prm Telegram – SAP 61
This function is used to set the parameters of a slave at startup, after a
restart or system reset, and at any time except within data exchange mode.
At a minimum, the parameterization telegram contains 7 bytes of specific
information required by the ProfiBus standard. This includes: Response
Monitoring/Watchdog Time T
WD
, T
SDR
time for Master/Slave timing,
Freeze/Sync Mode Enable/Disable, Lock/Unlock Slave for this Master,
Group Assignment, Master Address, and Identification Number. Additionally,
it may also contain other user-related parameters in bytes 8 to 32, or up to
244.
Set_Prm Parameterization Telegram With Header
SD LE LEr SD DA SA FC DSAP SSAP
DU FCS ED
68H X X X 8x 8x X 3DH
(61)
3EH
(62)
X.. X 16H
Note that with SRD transmission, the DSAP specifies the Set_Prm
function (61) request, while the SSAP requests that the Chk_Cfg function
(62) follows (return response).
Set_Prm Parameterization Telegram DU Byte 1 – Station_status
76 5 43210
Lock_Req Unlock_Req Sync_Req Freeze_Req WD_On
Reserved –Set to 0
WD_Fact_1
WD_On (Watchdog On):
Set this bit to 1 to activate the watchdog control.
Refer to the Watchdog section for more information.
Freeze_Req (Freeze Mode Request):
If this bit is set, the slave will operate
in the Freeze Mode as soon as the Global_Control function is received.
If a slave does not support the Freeze control, it sets the
Diag.Not_Supported bit within the diagnostic information.
Sync_Req (Sync Mode Request):
If this bit is set, the slave will operate in
Sync Mode as soon as the Global_Control function is received. If a
slave does not support the Sync control, it sets the Diag.Not_Supported
bit within the diagnostic information.
Unlock_Req (Unlock Request):
See Table below.
Lock_Req (Lock Request):
See Table below.
Lock
Bit 7
Unlock
Bit 6 Description
0 0 The Min T
SDR
parameter may be changed. All other
parameters remain unchanged.
0 1 DP Slave is unlocked/released for other masters.
1 0 DP Slave locked for other masters. All parameters are
accepted and can be carried over (except min T
SDR
= 0).
1 1 DP Slave is unlocked/released for other masters.
Set_Prm Telegram DU Byte 2 – WD_Fact_1, Range 1 to 255
76543210
XXXXXXXX
WD_Fact_1