Page view 42
43
AS-Interface
components for
safety at work
The concept of “
safety at work
” permits
integration of safety-related compo-
nents such as emergency stop buttons,
guard door switches, or safety light
grids, to be connected directly into a
standard or V2.1 AS-Interface network.
These components are fully compatible
with the standard AS-Interface compo-
nents i.e. master, slaves, power supply
unit, repeater, etc. according to EN
50295. This new range of safety com-
ponents has been designed and certi-
fied to comply with the relevant Euro-
pean and international safety standards.
Siemens can offer and supply all rele-
vant components to construct a safe
AS-Interface network solution.
Safety monitor
The safety monitor is designed to react
on the information transmitted via AS-
Interface, i.e. master call and response
from the safety slave, and stops the
plant in a safe state should the safety
circuit be interrupted or the safety sen-
sor malfunctions.
For standard AS-Interface bus stations, the
master still performs the data transmis-
sion function between a PLC and the sta-
tions on the bus (sensors and actuators).
Safe modules type K45
The safe compact module K45F is
equipped with two “safe” inputs. For
operation up to safety category 3 it is
possible to assign both inputs sepa-
rately. If category 4 is required, a dual-
channel input is available on the module
via an M12 connection.
PRODUCT OVERVIEW
Page view 42