What to do if something
goes wrong
Errors can occur even in the best sys-
tems. In AS-Interface too, there are error
patterns that are usually easy to detect
and just as easy to eliminate. The only
error that AS-Interface cannot recognise
is the failure of a binary sensor or actu-
ator integrated in a module.
A defective slave can simply be re-
placed by a new slave. An AS-Interface
cable break will of course result in the
failure of slaves. By locating their posi-
tion it is possible to find the cable break
because the slaves located beyond the
interruption point from the point of view
of the master can then no longer be ad-
dressed.
A short circuit can have a disastrous ef-
fect on the system. The master there-
fore recognises a short circuit by the
APF bit (AS-Interface Power Fail) and
immediately takes action. All slaves im-
mediately go into the status “not ac-
tive”. For the actuators that means that
power stops flowing.