Tip 5 – Routing of the cable
When laying the AS-Interface cable please note the following:
• Always use the yellow profiled AS-Interface cable where possible, brown
for “+” and blue for “-”.
• Even whilst communication along the AS-Interface cable offers a high
degree of EMC immunity, it should still be routed away from power cables,
even in the control cabinet!
• Every AS-Interface line requires its own cable. AS-Interface cables must
not be laid together with others in a bus cable.
• If individual cores are used (e.g. in the control cabinet), always lay parallel
core pairs. In standard stranded wires, lay individual cores together or twist
them.
Tip 6 – Ensuring EMC
Connect all inductance’s, e.g. contactor and relay coils, valves, brakes, with
suppresser diodes, varistors or RC elements. If frequency converters are
used, always use network filters, output filters, and shielded motor cables.
Tip 7 – Sensor and actuator power
Sensors and actuators must be supplied directly from the associated input
or out-put of the slave. The cables should be kept as short as possible and
away from energy cables, i.e. the slave modules should be as close as
possible to the sensors and actuators.
Tip 8 – Installation of frequency converters
• Always follow the assembly guidelines in the operating instructions.
• Connect the cable shield, e.g. between filter and frequency converter and
between the frequency converter and the motor, directly at both ends with
a large contact surface, and with a sufficient cross section (at least 4mm
2
).
• Connect all metal parts to system ground.
Tip 9 – System expansion 2.1
With masters to Specification 2.1 it is possible to operate A/B slaves and
analog slaves according to Definition 7.3/7.4 (only as standard slaves).
Tip 10 – Status/diagnostics
For speedy diagnostics, the status and diagnostics bits should be analysed
in the PLC.