How to configure an Anybus PROFIBUS Slave module with a Siemens Step7 PLC
SCM-7032-026
Rev 2.1
Appendix 2 Errors and diagnostics
The LED:s on the Anybus-S Slave module
The LED:s on the Anybus-S Slave module have the meaning shown in Figure 31.
Figure 31 Indication LEDs on the Anybus-S module
LED #
Name Colour Meaning Corrective actions
n
Not used
o
On-Line Green
Indicates that the module is On-Line on the
fieldbus.
Solid Green - Module is On-Line and data
exchange is possible.
Turned Off - Module is not On-Line
No actions needed
p
Off-Line Red
Indicates that the module is Off-Line on the
fieldbus.
Solid Red - Module is Off-Line and no data
exchange is possible.
Turned Off - Module is not Off-Line
Check hardware, i.e. cable
connection, baudrate setting
etc.
Check hardware configuration
in Step7
q
Fieldbus
Diagnostics
Red
Indicates certain faults on the Fieldbus side.
Flashing Red 1 Hz - Error in configuration:
IN and/or OUT length set during initialisation
of the module is not equal to the length set
during configuration of the network.
Flashing Red 2 Hz - Error in User Parameter
data: The length/contents of the User
Parameter data set during initialisation of the
module is not equal to the length/contents set
during configuration of the network.
Flashing Red 4 Hz - Error in initialisation of
the PROFIBUS communication ASIC.
Turned Off - No diagnostics present
Check hardware configuration
in Step7
If
Flashing Red 4 Hz consult
HMS
www.anybus.com HMS Industrial Networks AB
Page 25 (30)