How to configure an Anybus PROFIBUS Slave module with a Siemens Step7 PLC
SCM-7032-026
Rev 2.1
5.1.1 I/O configuration
The choice of module(s) you like to use depends on what your application demand is. It is possible to choose
these modules freely and to compose the I/O sizes needed, se examples below in table 1.
Bytes needed by the application Modules to use
4 In + 2 Out 4 In + 2 Out
7 In + 12 Out 4 In + 2 In + 1 In + 8 Out + 4 Out
32 In + 32 Out 32 In/Out
68 In 64 In + 4 In
Note: Reading or writing more than four bytes consistent data from the I/O image, see the next chapter. For
all Anybus PROFIBUS modules except the Anybus-CompactCom, more than 2 bytes of consistent data is
only supported when using the Universal module.
Expand the Anybus-S PDP tree in the navigation list to the right. The modules are then composed together in
the “module list” of the Anybus as shown in the figure below.
Figure 13 Selecting In and Out modules with “Drag and Drop”.
By double clicking on a module in the “module list” it is possible to set the offset addresses. See example in
Figure 14.