Siemens RDF300…/RDF340.../RDF400… Room Temperature Controllers N3076en
Building Technologies 11 July 2008
Disposal
The device is classified as waste electronic equipment in terms of the European Direc-
tive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste.
The relevant national legal rules are to be adhered to. Regarding disposal, use the
systems setup for collecting electronic waste.
Observe all local and applicable laws.
Technical data
Operating voltage
RDF300…/RDF400…
RDF340…
AC 230 V +10/-15 %
SELV AC 24 V ± 20 %
Frequency 50/60 Hz
Power consumption Max. 8 VA
Fan control Q1, Q2, Q3-N
Rating
AC 230 V
Max. 5(2) A
Control output Y11-N/Y21-N (N.O.)
Rating
AC 230 V
Max. 5(2) A
Control output Y10-G0/Y20-G0
Resolution
Current
SELV DC 0…10 V
39 mV
Max. ± 1 mA
Multifunctional input X1-M/X2-M
Temperature sensor input:
Type
Digital input:
Operating action
Contact sensing
Insulation against mains voltage (SELV)
QAH11.1 (NTC)
Selectable (N.O./N.C.)
SELV DC 0...5 V/max 5 mA
4 kV, reinforced insulation
Function input:
External temperature sensor, heating/cooling changeover
sensor, operating mode switchover contact, dewpoint
monitor contact, enable electrical heater contact, alarm
contact
Selectable
Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2 K (0.5...6K)
1 K (0.5...6K)
Setpoint setting and range
Comfort mode (P08)
Energy Saving mode (P11-P12)
Standby (P65-P66)
21°C (5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF (OFF, 5...40 °C)
Multifunctional input X1/X2
Input X1
Input X2
Selectable 0…6
3: (P38) operating mode
switchover
2: (P40) heating/cooling
changeover sensor
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
± 3.0 K
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Power supply
Outputs
Inputs
Operational data