Alarms, faults and system messages
9.3 Faults
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
295
Extended settings for faults
Table 9- 8 Advanced settings
Parameter Description
You can change the fault response of the motor for up to 20 different fault codes:
p2100 Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
p2101 Setting, fault response
Setting the fault response for the selected fault
You can change the acknowledgement type for up to 20 different fault codes:
p2126 Setting the fault number for the acknowledgement mode
Selecting the faults for which the acknowledgement type should be changed
p2127 Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
You can change up to 20 different faults into an alarm or suppress faults:
p2118 Setting the message number for the message type
Selecting the message for which the message type should be selected
p2119 Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
You will find details in function diagram 8075 and in the parameter description of the List
Manual.