Functions
7.9 Application-specific functions
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
234 Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
7.9.2.4 Dynamic braking
Dynamic braking is typically used in applications in which dynamic motor behavior is
required at different speeds or continuous direction changes, e.g.:
Horizontal conveyors
Vertical and inclined conveyors
Hoisting gear
Principle of operation
The inverter controls the braking chopper depending on its DC link voltage. The DC link
voltage increases as soon as the inverter absorbs the regenerative power when braking the
motor. The braking chopper converts this power into heat in the braking resistor. This
therefore prevents the DC link voltage increasing above the limit value V
DC link, max
.
%UDNLQJPRGXOHDFWLYH
0RWRUSRZHU
PRWRUL]HG
UHJHQHUDWLYH
6SHHG
'&OLQNYROWDJH8
DC
8
DC, max
U
U
W
W
W
W
Figure 7-13 Simplified representation of dynamic braking with respect to time
Braking resistor connection
Connect the braking resistor to terminals R1 and R2 of the Power Module
Ground the braking resistor directly to the control cabinet's grounding bar. It is not
permissible that the braking resistor is grounded via the PE terminals on the Power
Module.
If you must observe the EMC guidelines, pay special attention to the shielding.