Functions
7.9 Application-specific functions
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
227
Braking with regenerative feedback into the line
supply
The inverter feeds the regenerative power back into
the line supply.
Advantages:
Constant braking torque; the
regenerative power is not converted into heat, but
is regenerated into the line supply; can be used in
all applications; continuous regenerative
operation is possible - e.g. when lowering a crane
load
Disadvantage:
Does not function when power
fails
a
a
,QYHUWHU
/LQH
%UDNH
SRZHU
/RDG
0RWRU
,QYHUWHU
0
Braking with regenerative feedback into
the line supply
Braking method depending on the application
Table 7- 33 What Power Module is suitable for what application?
Application examples Electrical braking methods Power Modules that can be
used
Pumps, fans, mixers,
compressors, extruders
Not required PM230, PM240, PM250,
PM260
Grinding machines, conveyor
belts
DC braking, compound braking PM240
Dynamic braking PM240 Centrifuges, vertical conveyors,
hoisting gear, cranes, winders
Braking with regenerative feedback
into the line supply
PM250, PM260