Functions
7.4 Setpoint sources
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
196 Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
7.4.2 Motorized potentiometer as setpoint source
The 'motorized potentiometer' (MOP) function simulates an electromechanical potentiometer
for entering setpoints. You can continuously adjust the motorized potentiometer (MOP) using
the control signals "raise" and "lower". The control signals are received via the digital inputs
of the inverter or from the operator panel that has been inserted.
Typical applications
Entering the speed setpoint during the commissioning phase.
Manual operation of the motor should the higher-level control fail.
Entering the speed setpoint after changeover from automatic operation to manual
operation.
Applications with largely constant setpoint and without higher-level control.
Principle of operation
023GRZQ
3
023XS
3
2))GRZQUDPS
023U
212))
Q
PD[
3
Q
PD[
3
3 3
W
W
W
W
Figure 7-9 Function chart of motorized potentiometer
Motorized potentiometer parameters
Table 7- 16 Basic setup of motorized potentiometer
Parameter Description
p1047 MOP ramp-up time (factory setting 10 s)
p1048 MOP ramp-down time (factory setting 10 s)
p1040 Start value of MOP (factory setting 0 rpm)
Determines the start value [rpm] that becomes effective when the motor is switched
on