Technical data for accessories:
3VU13 3VU16
Undervoltage Release
Consumption During Pick-up VA/W 10/6
Consumption During Running VA/W 4.7/2
Dropout V 0.7 to 0.35 X Ue
Pickup V 85 to 110% of Ue
Max Operating Time ms 20
Shunt Release
Consumption VA/W 10/6
Max Continuous Rating Sec 5
Pickup V 0.7 to 1.1 X Ue
Current Limiter for 3VU13
Rated current In 56 Amps
Rated Voltage Ue 500 V, 50 / 60 Hz.
Power Connection mm
2
2 x (1 to 6)
Mounting
on DIN Rail in any position.
Table 1 3VU13/3VU16 breaking capacity at 415V
3VU13
Rated current A 0.16-1 1.6 2.4 3.2-4 5-6 8-10 13-16 20-25
Rated Short circuit breaking capacity @ 415V
Icu kA 100 100 100 100 100 10(50) 6(50) 6(50)
Ics kA 100 100 100 100 100 10(50) 6(50) 6(50)
Maximun back up fuse (gL/gG)
Diazed A *****808080
NHA*****808080
( ) Values in bracket are with current limiter; * Fuse not required
For 3VU13 breakers of ratings 8A & above, in place of fuses, the Current Limiter can be used to increase the S/C breaking capacity.
Rated Breaking Capacity DC; t = 15ms
1 Contact 2 Contacts 3 Contacts
in series in series 10 kA
110-150V 220-300V 330-450V
3VU16
Rated current A 1.6-2.4 4 6 10 16 25 32-63
Rated Short circuit breaking capacity @ 415V
Icu kA 100 100 100 100 100 100 35
Ics kA 100 100 100 100 100 50 17
Maximun back up fuse (gL/gG); * Fuse not required
Diazed A * * * * * * -
NHA******200
Rated Breaking Capacity DC; t = 15ms, upon enquiry