ACVATIX™
Electromotoric actuators
for small valve types VVP45.., VXP45.., VMP45..
(DN £ 25, k
VS
£ 6,3 m
3
/h)
SSB31..
SSB81..
SSB61..
· SSB31.. operating voltage AC 230 V 3-position control signal
· SSB81.. operating voltage AC 24 V 3-position control signal
· SSB61.. operating voltage AC / DC 24 V DC 0…10 V control signal
· Nominal force 200 N
· Automatic identification of valve stroke
· Direct mounting with union nut, no tools required
· Basic types complete with plug-in connecting cable, length 1.5 m
· Optional cable types
· Cable length 1.5 m, 2.5 m and 4.5 m
· Halogen-free cables
· Manual override and position indication
· Parallel connection of multiple actuators possible
· Auxiliary switch integrated in SSB31.1 and SSB81.1 actuators
Use
For operation of Siemens valves V..P45.. for water-side control of hot and cooling water
in heating, ventilation and air conditioning systems.
Page view 0
1 2 3 4 5 6 7 8 9 10

Summary of Contents

Page 1 - SSB61

CA1N4891en2014-11-10Building Technologies4891SSB.. without auxiliary switch SSB..1 with auxiliary switchACVATIX™Electromotoric actuatorsfor small valv

Page 2

10/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10ã Siemens Switzerland Ltd, 2004 Subject tochange

Page 3 - The cable connector

2/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10Type summaryType reference OperatingvoltageRun time at50 HzControlsig

Page 4 - 4.5...5 mm

3/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10Function / mechanical designWhen the actuator is driven by DC 0…10 V

Page 5

4/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10NotesThe actuators must be electrically connected in accordance with

Page 6

5/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10A 3 mm hexagonal socket wrench can be used to move the actuator to an

Page 7 - 4891Z28en

6/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10Technical dataSSB31.. SSB81.. SSB61..Power supply Operating voltage

Page 8 - (Y1) (Y2)

7/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10General ambientconditionsOperationEN 60721-3-3TransportEN 60721-3-2St

Page 9

8/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10Recommended connecting cable: H03VV-F, 2x0.5…0.75 mm2.Connection diag

Page 10

9/10Siem ens Electrom otoric actuators CA1N4891enBuilding Technologies 2014-11-10DimensionsAll dimensions in mm8381.44891M0172.5489G¾98.583484891M0289

Comments to this Manuals

No comments