Motor Protection Circuit Breakers
3VU13 and 3VU16
3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU
motor protection circuit breakers are used for protection of motor against overload, single phasing and
short-circuit faults.
Applications
Motor Protection
Circuit breakers type 3VU13 & 3VU16 offer overload, short
circuit and phase loss protection for 3 phase motors upto 11kW
and 22 kW respectively. The breaker has a toggle switch for
ease of operation and can be offered with auxiliary contacts,
trip indicating contacts, U/V or Shunt release. High breaking
capacity of 100kA is available in 3VU13 upto 6A and in 3VU16
upto 25A.
Distribution Feeder Protection
Standard version of 3VU13 and 3VU16 has adjustable O/L and
fixed S/C release. Main application is for disconnection and
protection of the distribution feeders, upto 25A and 63A
respectively. A large number of overlapping ranges are
available for offering closer protection to various loads.
Transformer protection
A separate 3VU13 range can be offered to protect the primary
side of the transformers. The range is available upto 20A. To
take care of the inrush current due to transformer switching,
the S/C release is set at 19 times the rated current unlike 12
times of the rated current available in standard range.
Fuse Monitoring
3VU1340-1MS00 is offered for Fuse Monitoring application.
This device is connected in parallel to the fuses. In case one of
the fuses blows, the rated current will flow through the
corresponding phase of this MPCB. MPCB, through its auxiliary
contacts, provides a tripping signal to the contactor and thus
the motor will be switched off. Hence, the motor will be
protected from single phasing. (Refer page 51 for connection
diagram)
Standard
3VU motor protection circuit breakers confirm to IS/IEC 60947-1,
IS/IEC 60947-2, IS/IEC 60947-4-1, DIN VDE 0660
Range
3VU13: 0.16 - 25A
3VU16: 10 - 63A
Benefits and features
High performance
Instantaneous Tripping
3VU circuit breakers operate on the Current Limiting
Principle.
Current Limiting Principle
In case of short-circuit condition motor protection circuit
breaker trips before the short-circuit current reaches the
prospective peak. Hence, for circuit breaker to be current
limiting it must interrupt the short-circuit current in half cycle
or less as shown below.
3VU13/16
Fuse Monitoring MPCB - 3VU1340-1MS00