Satronic TF830.3 - OIL BURNER
CONTROLLER
Oil burner control•
Plug in base (SA7531001)•
Single stage operation•
MZ 770S / UVD 970 Flame detector •
Pre - purge 12 seconds•
Post ignition time 2 - 5 seconds•
Manual reset from lockout•
240 volt AC•
#SA02231
1
A Honeywell Company
For 1- or 2-stage oil power burners up to 30kg/
h capacity and intermittent operations.
Flame detection:
- Photoresistor MZ 770 S
- Infrared-flicker detector IRD 1010.1
- UV solid state sensor UVD 970
Oil Burner Safety Control
TF 830.3 / 832.3
TECHNICAL DATA
Operating voltage 220/240 V (-15..+10%)
50 Hz (40-60Hz)
Fuse rating 10 A fast, 6 A slow
Power consumption ca. 5 VA
Max. load per output
- terminal 3 1.5 A, cos ϕ 0.2
- terminal 4 4.0 A, cos ϕ 0.4
- terminal 5 0.5 A, cos ϕ 0.4
- terminal 6 0.5 A, cos ϕ 0.4
- terminal 7 0.1 A, cos ϕ 0.4
total load 5.0 A, cos ϕ 0.4
Pre-purge time ca. 12 sec.
Pre-ignition time ca. 12 sec.
Post-ignition time TF 830.3 ca. 20 sec.
TF 832.3 ca. 2-5 sec
Delay time to oil valve 2 40 sec. (TF 832.3)
Lockout safety time 10 sec.
Reset time from lockout ca. 90 sec
Flame detector:
MZ 770 S side-on and end-on viewing
Light sensitivity MZ 770 S > 6 Lux
IRD 1010.1 side-on or end-onviewing
UVD 970 end-on viewing
Sensor operating current min. 30 µA
Weight incl. wiring base 0.25 kg
Mounting position any
Protection class IP44
Recommended ambient operating
temperature for control and
flame detector 0°C...+60°C
approved and certified according
to European standards EN 230
APPLICATION RANGE
The TF 830.3 or TF 832.3 oil burner safety control boxes
are suitable to control and monitor oil power burner up to
30 kg/h capacity (approved and certified according to
EN230).
TYPES AVAILABE
TF 830.3 1-stage operation
post-ignition time ca. 20 sec.
low voltage protection according to EN230
TF 832.3 2-stage operation
post-ignition time 2-5 sec.
low voltage protection according to EN230
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plastic housing. It incorporates the thermo-
mechanical, temperature compensated timer, flame check
and reset circuits.
Manual reset from lockout is provided by a push button with
an integrated lockout signal lamp. A central fixing screw
locks the control box to the wiring base. The wiring base and
control box have a positive plug-in arrangement, making it
impossible to achieve an incorrect connection between the
two parts. A variety of cable entry points provides utmost
flexibility of electrical wiring.
The TF 832.3 is fully compatible with the TF 730,
730-1 and TF 832.
An optional extension button (item no. 70601)
compensates for height differences to the TF 730
series.
EN1C-0145SZ20 R0405
Programmed oil & gas Burner Controls
System Control Engineering NZ Ltd For Gas Combustion & Control Equipment
Tel : 09-636-1401 • Fax: 09-636-1525 • [email protected] • www.systemcontrol.co.nz
Satronic TF832.3 - OIL BURNER
CONTROLLER
Oil burner control•
Plug in base (SA7531001)•
2 stage operation•
MZ770S / UVD 970 Flame detector •
Pre - purge 12 seconds•
Post ignition time 2 - 5 seconds•
Manual reset from lockout•
240 volt AC•
#SA02431
OBSOLETE USE #SA0312005
DKO 972 MOD.5 OIL BURNER
CONTROLLER
Plug in Base ( SA7531001)•
2 Stage Operation•
MZ770/UVD970ame •
detectors
Pre- Purge 15 seconds•
Safety Time 5 seconds•
Post Ignition time (afterV1) •
7 seconds
Delay time to V2 20 seconds.•
Pre Purge 15 seconds•
#SA0312005
6.4
Section 6
Page view 3